2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
2.2.5 the entire set of action time (including the inherent time of the relay)
Time of motion of a fast moving segment:
1.2 times the value of the entire set of measurement, not more than 50ms
2.2.6 transient transcendence
No more than 5%
2.2.7 og measurement loop accuracy
Measurement and control device for installing special measurement sub module:
Current, voltage: 0.2
Power and electric degree: 0.5
2.3 insulation performance
2.3.1 insulation resistance
Device for charged and uncharged part and a casing and electrical contact of the circuit between the open circuit voltage of 500V megohm meter measuring the insulation resistance value, normal test atmospheric conditions, the circuits of each class of insulation resistance should not be less than 100m ohm.
2.3.2 medium strengthUnder normal test conditions, the device can withstand the frequency of 50Hz, voltage 2000V lasted 1 minutes of power frequency voltage withstand test without breakdown flashover and component damage. During the test, the other circuit is connected to the ground with the other circuit when the voltage is applied.
2.5 mechanical properties
2.5.1 vibration
The device can withstand the vibration endurance test of the I level of 16.3 in the GB7261.
2.5.2 impact
The device can withstand the impact endurance test of the I level of 17.5 in the GB7261.
2.5.3 collision
The device can withstand the impact endurance test of the GB7261 level of I in the eighteenth chapter.
2.6 environmental conditions
A) ambient temperature: Work: -40 C ~ 85.
Storage: 25 degrees to +70 degrees Celsius, in the limit value does not apply the amount of incentive, the device does not appear irreversible change
After the temperature is restored, the device should be able to work properly.
Relative humidity: the maximum monthly average relative humidity of 90%, while the average monthly average of.
The lowest temperature is 25 DEG C and no condensation surface. When the maximum temperature of +40 degrees Celsius, the average maximum relative humidity
Degree no more than 50%.
(c) atmospheric pressure: 86 to 106kPa (relative altitude below 2km)
Three、Software function deion
3.1. differential quick break protection
When any phase difference current is greater than the value of the differential speed, the protection action is stopped. Fast removal of generators in the case of a serious fault in the area of the generator. Differential speed determine the value should be able to avoid the external fault of the maximum unbalanced current, and taking into account the current transformer saturation factor, generally take 3 to 8 times the rated current
3.2.Ratio differential protection
Using the conventional ratio differential principle, the equations of motion are as follows:
Id > Icd (Ir Ir0)
Id - Icd > Kcd ·(Ir- Ir0) (Ir ≥ Ir0)
At the same time to meet the above two equations, the ratio of the differential element action. Among them, Id for the differential current, Ir for the braking current, Kcd for
Ratio braking coefficient, Icd is the threshold value of the differential current, and Ir0 is the turning point of the current value.
1)under the time limit: when the three-phase current is greater than the lower limit of the value of any phase, but not meet the anti time limit start value, press the lower limit delay action on the alarm **;
2) inverse time: when the three-phase current any phase current is larger than the inverse time starting value, according to the inverse time lag action equation I2-1 t is greater than or equal to K acts, type: I for the generator current standard? Value, K - generator stator winding allows thermal time constant.
3) the upper bound limit: when the three-phase current is greater than the upper limit value, the time limit is delayed by the time limit.
3.8 transverse differential protection
Generator transverse differential protection is usually used for the reaction of generator stator winding inter turn short circuit and a parallel windings open welding, protection from the generator neutral point between two branch imbalance fundamental current, but current is greater than fixed value setting delay action on the alarm or trip.