3.10 stator overvoltage protection
For generator, in particular to a hydro generator, after load rejection due to the speed control of speed control system can not keep up, is easy to appear the stator voltage exceeds the allowed range of over voltage phenomena; at this point to be equipped with over voltage protection, protection from the generator terminal voltage when any phase of more than setting value by setting the delay action to stop.
3.11 stator ground protection
Generator stator grounding protection can for the generator neutral point ungrounded or via arc suppression coil grounding grounding, protection from the generator end opening of the delta winding voltage when open delta windings voltage greater than setting value by setting the exit delay.
3.9 inverse time negative sequence overcurrent protectionPower system occur asymmetric short-circuit and three-phase load imbalance may be the negative sequence current flowing in the stator winding of the generator, and produce harmonic current in the rotor, rotor surface overheating caused, generator's inverse time negative sequence over the protection of rotor flow under the situation not long overheated rotor insulation degradation caused damage to the generator, discrimination protection of generator stator negative sequence current size, consists of three parts:
1) under the time limit: when the negative sequence current is greater than the lower bound value but does not meet the start value of the anti time limit, the alarm ** is delayed by the lower limit;
2) inverse time: when the negative sequence current is larger than the inverse time start value, according to the inverse time lag action equation I22-K t is equal to or larger than a action, type: I2-- generator negative sequence current standard? Value, K - generator operation value of negative sequence current in the standard, a generator rotor surface bear negative sequence current capability of constant;
3) the upper bound limit: when the negative sequence current is greater than the upper bound limit, the upper limit is delayed by the time delay.
1.3 function configurationFunction configuration of SAI3880D digital generator differential protection deviceDifferential quick break, ratio brake differential, CT disconnection locking differential, CT disconnection alarm, stator overvoltage protection, stator ground fault protection, overload alarm, anti time overcurrent protectionFunction configuration of backup protection device for SAI3881D digital generatorTransverse differential protection, loss of excitation protection, rotor one point grounding protection, rotor two points grounding protection composite voltage over current protection, inverse time negative sequence overcurrent protection, Pt disconnection alarm, non electricity protection (generator water shutoff, and the generator thermal, generator excitation accident, main steam valve closed),

2.2 Main technical performance
Precise working range of 2.2.1 sampling circuit (10% error)
Voltage: 0.4 V ~ 120V
Current: 0.08In20In
2.2.2 contact capacity
Signal circuit contact current carrying capacity 400VA
Signal circuit contact fault arc capacity 60VA
2.2.3 tripping current
Breaker trip current 0.5A~4A (order indication)
The circuit breaker closing current 0.5A~4A (the order stated)
2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz