1.3 function configurationFunction configuration of SAI3880D digital generator differential protection deviceDifferential quick break, ratio brake differential, CT disconnection locking differential, CT disconnection alarm, stator overvoltage protection, stator ground fault protection, overload alarm, anti time overcurrent protectionFunction configuration of backup protection device for SAI3881D digital generatorTransverse differential protection, loss of excitation protection, rotor one point grounding protection, rotor two points grounding protection composite voltage over current protection, inverse time negative sequence overcurrent protection, Pt disconnection alarm, non electricity protection (generator water shutoff, and the generator thermal, generator excitation accident, main steam valve closed),
3.9 inverse time negative sequence overcurrent protectionPower system occur asymmetric short-circuit and three-phase load imbalance may be the negative sequence current flowing in the stator winding of the generator, and produce harmonic current in the rotor, rotor surface overheating caused, generator's inverse time negative sequence over the protection of rotor flow under the situation not long overheated rotor insulation degradation caused damage to the generator, discrimination protection of generator stator negative sequence current size, consists of three parts:
1) under the time limit: when the negative sequence current is greater than the lower bound value but does not meet the start value of the anti time limit, the alarm ** is delayed by the lower limit;
2) inverse time: when the negative sequence current is larger than the inverse time start value, according to the inverse time lag action equation I22-K t is equal to or larger than a action, type: I2-- generator negative sequence current standard? Value, K - generator operation value of negative sequence current in the standard, a generator rotor surface bear negative sequence current capability of constant;
3) the upper bound limit: when the negative sequence current is greater than the upper bound limit, the upper limit is delayed by the time delay.
2.4 electromagnetic compatibility
2.4.1 electrostatic discharge reactance
Through the GB/T 17626.21998 standard, electrostatic discharge immunity test IV.
2.4.2 radio frequency electromagnetic field radiated immunity
Through the GB/T 17626.31998 standard, RF electromagnetic field immunity test level 3.
2.4.3 electric fast transient pulse group immunity
GB/T 1998 - 17626.4 standard, electrical fast transient pulse group immunity test.
2.4.4 surge (impact) immunity
Through the GB/T 1999 - 17626.5 standard, surge (impact) immunity test 3.
Conduction disturbance degree of 2.4.5 RF field induction
Through the GB/T 17626.61998 standard, RF induction level 3 test conducted
2.4.6 power frequency magnetic field immunity
Through the GB/T 1998 - 17626.8 standard, the power frequency magnetic field immunity 5 level test
2.4.7 pulse magnetic field immunity
Through the GB/T 1998 - 17626.9 standard, the pulse magnetic field immunity 5 level test.
2.4.8 damped oscillatory magnetic field immunity
Through the GB/T 1998 - 17626.10 standard, damped oscillatory magnetic field immunity test 5 levels of test.
2.4.9 oscillation wave immunity
Through the GB/T 1998 - 4 standard, 17626.12 - level oscillation wave immunity test.
device overview
SAI3880D series digital generator protection device with high performance chip supports universal hardware platform, easy to maintain; the Ethernet communication, high-speed data transmission and reliable. Complete localization of Chinese display technology, simple operation.
Based on waterproof, dust, anti vibration design, can be run in a variety of field conditions.
Suitable for capacity of 50MW and below the fire and hydro generator protection.
1.2 main features of the device
An Motorola 32 bit microcontroller technology, the stability and speed of products is guaranteed
The protection. The 14 bit a / D converter, optional measurement module dedicated to the A / D conversion accuracy is up to 24 bits and the measurement indicators easily reach
The purpose of configuration with high capacity RAM and Flash Memory, can record 8 to 50 recorded reports, record the number of events is not less than 1000
An independent tuning of 32 sets of protection setting value, safe and convenient switch
In high precision clock chip, and equipped with GPS hardware circuit for the whole time, system clock synchronization
It is equipped with high speed Ethernet communication interface, and the integration of IEC870-5-103 standard communication protocol
In the electrical design with the machine, no adjustable device
In high grade, quality assurance component selection
An excellent anti-interference performance, panel or installed in the switch cabinet without other anti-jamming module
The purpose of self diagnosis function perfect
The chassis design of waterproof and dustproof and anti vibration.
The purpose of debugging conceptual design