2.4 electromagnetic compatibility
2.4.1 electrostatic discharge reactance
Through the GB/T 17626.21998 standard, electrostatic discharge immunity test IV.
2.4.2 radio frequency electromagnetic field radiated immunity
Through the GB/T 17626.31998 standard, RF electromagnetic field immunity test level 3.
2.4.3 electric fast transient pulse group immunity
GB/T 1998 - 17626.4 standard, electrical fast transient pulse group immunity test.
2.4.4 surge (impact) immunity
Through the GB/T 1999 - 17626.5 standard, surge (impact) immunity test 3.
Conduction disturbance degree of 2.4.5 RF field induction
Through the GB/T 17626.61998 standard, RF induction level 3 test conducted
2.4.6 power frequency magnetic field immunity
Through the GB/T 1998 - 17626.8 standard, the power frequency magnetic field immunity 5 level test
2.4.7 pulse magnetic field immunity
Through the GB/T 1998 - 17626.9 standard, the pulse magnetic field immunity 5 level test.
2.4.8 damped oscillatory magnetic field immunity
Through the GB/T 1998 - 17626.10 standard, damped oscillatory magnetic field immunity test 5 levels of test.
2.4.9 oscillation wave immunity
Through the GB/T 1998 - 4 standard, 17626.12 - level oscillation wave immunity test.
2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
2.2.5 the entire set of action time (including the inherent time of the relay)
Time of motion of a fast moving segment:
1.2 times the value of the entire set of measurement, not more than 50ms
2.2.6 transient transcendence
No more than 5%
2.2.7 analog measurement loop accuracy
Measurement and control device for installing special measurement sub module:
Current, voltage: 0.2
Power and electric degree: 0.5
2.3 insulation performance
2.3.1 insulation resistance
Device for charged and uncharged part and a casing and electrical contact of the circuit between the open circuit voltage of 500V megohm meter measuring the insulation resistance value, normal test atmospheric conditions, the circuits of each class of insulation resistance should not be less than 100m ohm.
2.3.2 medium strengthUnder normal test conditions, the device can withstand the frequency of 50Hz, voltage 2000V lasted 1 minutes of power frequency voltage withstand test without breakdown flashover and component damage. During the test, the other circuit is connected to the ground with the other circuit when the voltage is applied.